HTM 05-02: Appendix E: Construction and fixing of cavity barriers / Appendix F: Fire behaviour of insulating core panels

Firecode - Guidance in support of functional provisions (Fire safety in the design of healthcare premises) · PDF pages 94–96 of 112 · Source file: HTM_05-02_2015.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 05-02 – PDF page 94]

Appendix E: Construction and fixing of cavity

barriers

Cavity barriers should also be fixed so that their performance is unlikely to be made ineffective by:

Every cavity barrier should be constructed to provide at least 30 minutes’ fire resistance except for a cavity barrier in a stud wall or partition, which may be formed of:

a. movement of the building due to

a. steel at least 0.5 mm thick; or

b. timber at least 38 mm thick; or

subsidence, shrinkage or temperature change, and movement of the external envelope due to wind;

c. polythene-sleeved mineral wool or

b. collapse in a fire of any services

penetrating them;

c. failure in a fire of their fixings; or

mineral wool slab – in either case under compression when installed in the cavity; or

d. calcium silicate (cement-based or

d. failure in a fire of any material or

gypsum-based boards at least 12.5 mm thick).

A cavity barrier may be formed by any construction provided for another purpose if it meets the provisions for cavity barriers.

construction which they abut. For example, if a suspended ceiling is continued over the top of a fire-resisting wall or partition, and direct connection is made between the ceiling and the cavity barrier above the line of the wall or partition, premature failure of the cavity barrier can occur when the ceiling collapses. However, this does not arise if the ceiling is designed to provide fire protection of 30 minutes or more.

Cavity barriers should be tightly fitted to rigid construction and mechanically fixed in position wherever possible. Where this is not possible (for example in the case of a junction with slates, tiles, corrugated sheeting or similar materials), the junction should be fire-stopped.

[HTM 05-02 – PDF page 95]

Appendix F: Fire behaviour of insulating core

panels

Introduction

Unlike other buildings, healthcare premises (in particular hospitals) often utilise progressive horizontal evacuation rather than total building evacuation. Selecting the appropriate insulated core products for internal walls or partitions, or for external cladding material, is vital for patient and building occupant safety.

Insulating core panel systems are used for external cladding as well as for internal structures. However, while both types of panel system have unique fire behaviour characteristics, both can present particular problems with regard to fire spread.

Fire behaviour of the core materials and fixing systems

Panels typically consist of an inner core sandwiched between, and bonded to, a membrane such as facing sheets of galvanised steel. The panels are then formed into a structure by jointing systems, usually designed to provide an insulating and/or hygienic performance. The panel structure can be free- standing, but is usually attached to the building structure by lightweight fixings and hangers.

The most common forms of insulation in present use are:

• expanded polystyrene;

The use of cladding panels for both internal and external walls can produce a significant risk to the occupants of healthcare buildings, in particular in-patients who may be dependent on staff for evacuation. In considering the use of such cladding, reference should be made to the requirements of Approved Document B. The panel in-fill material, when involved in a fire, should not compromise the safety of occupants remaining in the building either through fire or through smoke spread.

• extruded polystyrene;

• polyurethane; and

When compared with other types of construction technique, these panel systems therefore provide a unique combination of problems for firefighters, including:

• mineral fibre.

• hidden fire spread within panels with thermoplastic cores;

However, panels with the following core materials are also in use:

• polyisocyanurate; and

• production of large quantities of black toxic smoke;

• modified phenolic.

• rapid fire spread leading to flashover; and

[HTM 05-02 – PDF page 96]

• they are hidden fire behind lining systems.

(ii) hot areas;

(iii) fire breaks in combustible panels;

Wherever possible, cladding with a non- combustible core should be used.

(iv) fire-stop panels;

(v) general fire protection;

Design recommendations

(vi) external cladding.

• All cores

(i) chill stores;

(ii) cold stores;

To identify the appropriate solution, a risk assessment approach should be adopted. This would involve identifying the potential fire risk within the enclosures formed by the panel systems and then adopting one or more of the following at the design stage:

(iii) clean rooms.

• removing the risk;

General

• separating the risk from the panels by an appropriate distance;

• providing a fire suppression system for the risk;

Generally, panels or panel systems should not be used to support machinery or other permanent loads. Any cavity created by the arrangement of panels, their supporting structure or other building elements should be provided with suitable cavity barriers.

• providing a fire suppression system for the enclosure;

• providing fire-resisting panels;

• specifying appropriate materials/fixing and jointing systems.

In summary, the performance of the building structure, including the insulating envelope, the superstructure, the substructure etc, must be considered in relation to their performance in the event of a fire.

Examples of possible solutions and general guidance on insulating core panel construction can be found in the International Association for Cold Storage Construction (European Division)’s ‘Design, construction, specification and fire management of insulated envelopes for temperature controlled environments’. While this document is primarily intended for use in relation to cold storage environments, the guidance, particularly in Chapter 8, is considered to be appropriate for most insulating core panel applications.

Specifying panel core materials

Note

Where at all possible, the specification of panels with core materials appropriate to the application will help to ensure an acceptable level of performance for panel systems when involved in fire conditions.

Core materials may be used in other circumstances where a risk assessment has been made and other appropriate fire precautions have been put in place.

The following are examples of core materials that may be appropriate to the application concerned.

• Mineral fibre cores

(i) cooking areas;