HBN 00-09: 3.0 Designing a healthcare facility: issues to consider – Engineering services
[HBN 00-09 – PDF page 32]
3.0 Designing a healthcare facility: issues to consider
3.164 There should be a strict routine for removing waste to ensure it does not remain uncollected for extended periods.
3.156 Storage for used linen should be in a clearly designated area separate from waste. This should minimise any risks of used linen being accidentally taken for disposal, or of waste being taken to the laundry.
Storage capacity 3.165 Storage areas need to be of a sufficient size to meet the needs of the number of different waste streams likely to be generated.
3.157 The waste and used linen storage areas should be able to be cleaned easily and efficiently. The holding area should be large enough to hold a wheeled-bin, which in turn will reduce handling and the subsequent risks to porters.
3.166 Storage capacity needs to match the proposed frequency of collection by a waste disposal contractor. The design of the facility should also take account of accessibility and space needed for vehicles collecting the waste.
Recommendations
3.158 A designated secure area is also necessary to hold receptacles from the whole site for collection for disposal and should be provided with good access routes away from public areas. This area should also be washable and animal-proof.
• Refer to Health Technical Memorandum 07-01 – ‘Safe management of healthcare waste’.
Waste receptacles 3.159 The size of waste receptacles required needs to be in line with the quantity of waste generated in a particular area by waste stream (that is, clinical or domestic waste).
• Waste receptacles should be foot-operated only (that is, it should not be possible to open them by hand in normal use) and should be easy to clean.
• The lids of clinical waste receptacles need to be capable of being cleaned and disinfected.
• Storage areas need to be of a sufficient size to meet the needs of the number of different waste streams likely to be generated in the healthcare facility.
3.160 Waste receptacles should be foot-operated only (that is, it should not be possible to open them by hand in normal use) and should be easy to clean. The foot pedal should be sturdy and durable. Staff training and awareness-raising on the risks of cross- infection will be key to understanding the importance of the receptacle’s hands-free operation and design.
3.161 The lids of clinical waste receptacles need to be capable of being cleaned and disinfected. Temporary labels should not be attached to receptacles as they inhibit effective cleaning.
Engineering services 3.167 This section discusses various aspects of engineering services and the IPC implications of each.
Clinical waste generated in primary care and community settings 3.162 In healthcare facilities such as care homes and primary care settings, all waste should be contained appropriately and kept secure at all times.
Planned preventative maintenance 3.168 In accordance with the HCAI Code of Practice, local policies should be in place for planned preventative maintenance to ensure safety and efficiency of the engineering services provided.
Heating/temperature control
3.163 The system and frequency of waste collection needs to be taken into account when planning facilities needed for temporary holding bays etc. If located externally, the holding bay or receptacle should be washable, secure and animal-proof. Only rigid lockable receptacles should be stored in external areas.
General 3.169 Covered heat emitters allow dust to build up beneath and inside the heat emitter grille. Where heat-emitter covers are used, regular planned cleaning should be undertaken to prevent dust
[HBN 00-09 – PDF page 33]
c. bronchoscopy and sputum induction rooms
where a risk assessment has indicated a tuberculosis risk;
accumulation. When installing heat emitters, it is recommended that there be sufficient space underneath the heat emitter to allow cleaning machinery to be used.
d. accommodation for highly
immunocompromised patients;
e. cardiac catheterisation/interventional
radiology units;
f. microbiology containment laboratories;
Pipework siting and access 3.170 Pipework should be contained in a smooth- surfaced box that is easy to clean; pipework sited along a wall can become a dust trap and be impossible to clean.
g. mortuaries.
3.171 Pipes and cables running through walls above suspended ceilings should be sealed as far as is practicable.
Split and cassette air-cooling units 3.176 Only units that are readily amenable to regular cleaning should be used. If installed, they should be cleaned as part of a regular planned maintenance scheme. Particular attention should be paid to the accessibility of the condensate drip-tray for cleaning.
Heating and general ventilation grilles 3.172 Ventilation grilles need to be accessed easily for inclusion in cleaning programmes by cleaning and estates staff.
Ventilation ductwork 3.173 Ventilation ductwork should be installed in such a way that it can be accessed for cleaning. Extract ductwork accumulates large amounts of dust, particularly where heat reclamation systems are used.
Chilled beam units 3.177 These comprise heat-exchange beams in a ceiling through which water is passed to cool or heat air that passes across them. They can be used as terminal devices on a mechanical ventilation system to cool or heat fresh air as it enters a room. If needed, they should be installed so that they can operate without generating condensate. They should be accessible for regular cleaning and maintenance.
Hot and cold water systems
See Health Technical Memorandum 03-01 – ‘Specialised ventilation for healthcare premises’ for comprehensive guidance on the design, installation and operational management of ventilation systems in healthcare premises.
See Health Technical Memorandum 04-01 Parts A and B for comprehensive guidance on the design, installation and operational management of water systems in healthcare premises.
3.178 The Water Supply (Water Quality) Regulations 2000 contain provisions to ensure that the drinking water supply within buildings to which the public has access remains wholesome and is not adversely affected by the local distribution system.
Specialised ventilation 3.174 In healthcare premises, certain activities will necessitate the provision of ventilation equipment with additional special features in order to achieve and maintain specific conditions. For infection prevention in specialist areas such as operating theatres, to prevent contaminated air from entering designated clean areas, it should be ensured that air flows from the cleanest to sequentially less clean areas. This direction of airflow prevents contaminated air passing in the opposite direction.
3.175 The following areas usually have specialised ventilation requirements for infection prevention:
a. operating departments;
3.179 Immunocompromised patients are at particular risk from cryptosporidium. Very low numbers of cryptosporidium cysts can occasionally occur in mains potable water. A local risk assessment could be used to establish the need for filtration of drinking water to remove these cysts. For guidance
b. airborne infectious diseases isolation;
[HBN 00-09 – PDF page 34]
3.0 Designing a healthcare facility: issues to consider
on separate cold water services for drinking water, see Health Technical Memorandum 04-01 Part A.
Sanitary facilities 3.183 WCs, bathrooms and showers should be designed to be easily cleaned and maintained. Wash- hand basins should be provided in or adjacent to WCs.
Storage and distribution of water 3.180 Many organisms capable of causing disease, particularly in highly susceptible patients (such as Pseudomonas aeruginosa and Legionella spp.), have been isolated from healthcare water systems. Preventative measures include:
3.184 Showers are generally more practical than baths in connection with clinical procedures and are easier to keep clean. Any fixture with a shower such as a seat should be readily amenable to cleaning.
• routine inspections of water storage tanks with cleaning as required;
3.185 To minimise the possibility of bacterial colonisation of showerheads, they should be regularly cleaned and descaled.
• identifying and removing dead-legs and blind ends;
• keeping cold water systems cold and hot water systems hot; and
• ensuring rapid turnover in water storage.
3.186 Bidets may present infection risks, depending on design and patient group (although they are most commonly installed in maternity units). The appliance should be rimless with an over-rim water supply and conform to the specifications given in Health Building Note 00-10 Part C.
3.187 Baths should be easy to clean. Recirculating spa pools are not recommended (see Health Building Note 00-10 Part C).
3.188 In wet rooms, high quality water-resistant cladding should be used on the walls to prevent mould.
3.181 Temperature control is the traditional strategy for reducing the risk from Legionella spp. in water systems. This will require temperature monitoring on a regular basis. The recommended test frequencies are given in Health Technical Memorandum 04-01 Part B. It is good practice to ensure that hot- and cold-water pipework is separated, insulated and preferably not in the same ducting to avoid heat transfer to the cold water supply.
Health Building Note 00-10 Part C contains guidance to assist the design team in the selection, specification and application of sanitary assemblies in healthcare buildings. It also gives guidance on the appropriate cleaning and maintenance regimes.
3.182 Chemical and other water treatments that have been shown to be capable of controlling Legionella spp. to some extent may also be considered. They will only work in systems that are amenable to their use (for example, those that do not have dead-legs and blind ends).
Health Building Note 00-02 gives detailed guidance on the design of sanitary facilities.
For guidance on control of Legionella in water systems, see the Health & Safety Executive’s (2000) ‘Legionnaire’s disease: the control of Legionella bacteria in water systems – Approved Code of Practice and guidance’.
Water fittings 3.189 Water fittings (washers etc) should not support microbiological growth. All fittings should satisfy the requirements of the Water Supply (Water Fittings) Regulations 1999. Even if WRAS-approved, the unnecessary use of flexible hoses should be avoided.
Health Technical Memorandum 04-01 Part B provides guidance on the monitoring and maintenance of water systems (including water storage).
See also Health Technical Memorandum 04-01 – ‘Addendum: Pseudomonas aeruginosa – advice for augmented care units’.
3.190 Where flexible hoses must be used (for example, on essential equipment such as hi-lo baths), they must be lined with a suitable alternative to EPDM (ethylene propylene diene monomer) as well as being WRAS-approved. Care should be taken to
[HBN 00-09 – PDF page 35]
sufficiently ventilated to retain the integrity of water seals.
avoid kinking or distorting them during installation (see DH Estates & Facilities Alert DH (2010) 03 – ‘Flexible water supply hoses’).
Ice for patient consumption 3.191 Ice machines should be of a type that dispenses ice by a non-touch nozzle.
3.199 The design should comply with the relevant British Standards and Codes of Practice, including BS EN 12056 and Approved Document H of the Building Regulations – ‘Drainage and waste disposal’. Recommendations for spatial and access requirements for public health engineering services are contained in CIBSE’s (2004) Guide G – ‘Public health engineering’.
3.192 Ice should be made directly from water that is of drinking quality. Ice for the immunocompromised should be made by putting drinking water into single-use ice-making bags, then into a conventional freezer.
3.200 Provision for inspection, rodding and maintenance should be located to minimise disruption or possible contamination, and access points should not be sited in clinical areas.
Bedhead services 3.193 Bedhead services should be smooth, accessible and easy to wipe clean.
3.194 Sufficient dedicated 13-amp socket outlets should be provided in corridors and in individual rooms to enable cleaning appliances with 9m long leads to operate over the whole department.
Bedpan washer-disinfectors/macerators 3.201 Where reusable bedpans are used, ward areas require adequate and suitable bedpan washer- disinfectors that comply with Choice Framework for local Policy and Procedures 01-01 Part D – ‘Management and decontamination of surgical instruments: washer-disinfectors’. Hands-free door- opening machines are recommended.
3.195 Where possible, socket outlets should be provided flush-mounted or in trunking systems to enable easy cleaning and prevent the build up of dust.
3.202 Where fitted, bedpan washer-disinfectors should be installed according to the Water Supply (Water Fittings) Regulations 1999 to prevent backflow and contamination. Easy access is essential.
Patient entertainment systems 3.196 Radio and television headsets should be capable of being cleaned or disinfected between patient use or should be single use, whichever is the most economical method to adopt.
3.203 When considering installation of bedpan macerators, it should be established that internal drains and the external sewerage system can cope with the resultant slurry.
See Health Technical Memorandum 08-03 – ‘Bedhead services’ for further guidance.
3.204 Where reusable supports are used with maceratable bedpans, there should be adequate facilities for their cleaning and disinfection between uses.
See also Appendix 1 on mental health settings.
Wastewater and sanitation 3.197 Wastewater is generated from a huge number of tasks carried out in healthcare buildings, which range from cleaning, hand-washing, specialist laundries, surgical operations and areas such as renal dialysis units. Most of this wastewater contains pathogenic microorganisms and must be disposed of via a safely contained internal drainage system into the external wastewater sewerage system.
Medical gas vacuum systems 3.205 Health Technical Memorandum 02-01 – ‘Medical gas pipeline systems’ gives guidance regarding piped medical gases and vacuum systems and includes recommendations on emergency procedures; power failure; access for cleaning contaminated vacuum systems; training and communication; maintenance and infection risk.
Internal drainage system 3.198 An internal drainage system should use the minimum amount of pipework, retain water and be airtight at joints and connectors. It should be
[HBN 00-09 – PDF page 36]
3.0 Designing a healthcare facility: issues to consider
Recommendations
Pneumatic-air tube transport systems 3.206 Guidance for the design and management of pneumatic transport systems can be found in Health Technical Memorandum 2009 – ‘Pneumatic air tube transport systems’.
• Refer to Health Technical Memorandum 04-01 Parts A and B for comprehensive guidance on the design, installation and operational management of water systems in healthcare premises.
3.207 The carrier for specimens should be transparent, able to be autoclaved and incorporate a leak-proof seal.
• Heat emitters should be designed and installed in a manner that prevents build-up of dust and contaminants.
• Heat emitters, heating and general ventilation grilles should be easily accessible for cleaning.
3.208 If leaking samples are allowed to enter the tube system or station, the station should be isolated and dealt with following advice from the IPC team. The disinfection procedure or cleaning will depend on the nature and level of risk imposed by the contaminant. Each incident will need to be assessed separately.
• WCs, bathrooms and showers should be designed to be easily cleaned and maintained. Wash-hand basins should be provided in or adjacent to WCs.
• To minimise the possibility of bacterial colonisation of showerheads, they should be regularly cleaned and descaled.
3.209 If clinical samples leak on entering or during transportation, the station and/or system should be isolated and dealt with following advice from the IPC team. Each incident will need to be assessed separately.
• Lighting should be planned so that units can be easily cleaned, with no ledges or ridges where dust can gather.
3.210 Major policy decisions with reference to the system should be made through the director of infection prevention and control (DIPC) and/or the IPC team.
• Contamination of the water supply can occur due to poor design of pipework, inappropriate storage or during renovation and refurbishment work (see Health Technical Memorandum 04- 01).
• Ice-making machines should not be installed in immunocompromised patient facilities. Ice for the immunocompromised should be made by putting drinking water into single-use ice- makers, then into a conventional freezer.
• With regard to pneumatic-air tube transport systems, the carrier for specimens should be transparent, able to be autoclaved and incorporate a leak-proof seal.