1 Introduction

Evidence base

Health Building Note 00 series of documents

1.8 This document is based on ergonomic research (published and unpublished) and the professional opinion of experts from the fields of architecture, ergonomics and nursing.

1.1 Health Building Notes give “best practice” guidance on the design and planning of new healthcare buildings and on the adaptation/ extension of existing facilities.

1.2 Core subjects are divided into specific topics and classified by a two-digit suffix and may be further subdivided into Supplements A, B etc. The Health Building Note 00 suite covers the core elements of healthcare buildings.

1.9 Many of the recommendations relating to the anthropometry of disabled people and their space requirements are based on (unpublished) research commissioned by the Department of the Environment and carried out by Robert Feeney Associates between 1997 and 2001 in support of BS 8300:2001.

Purpose and scope of this document

1.10 The recommendations relating to bed movement in corridors and through doors is based on a bed movement study commissioned by the Department of Health (DH) and carried out by Robert Feeney Associates. See Appendix 1 for details.

1.3 This document provides evidence-based best practice guidance on the design of circulation and communication spaces in healthcare buildings that are intended to be safe, accessible and fit for purpose.

1.11 Research/studies undertaken by Robert Feeney Associates were informed by anthropometric and strength measurement data from ‘ADULTDATA – The handbook of adult anthropometric and strength measurements’ (Department of Trade and Industry).

1.4 It includes design information on corridors, internal lobbies, internal stairs, lifts, handrails and doors that allow for the circulation of general traffic (see paragraphs 1.13–1.15), beds (see paragraphs 1.16–1.17) and patient trolleys.

Dimensions

1.12 All dimensions are in millimetres. The meaning of the abbreviation “ecw” used in the drawings is “effective clear width”.

1.5 Circulation spaces are corridors, internal lobbies etc within a department for moving between rooms/ spaces within that department. Communication spaces are hospital streets, corridors, internal lobbies, staircases etc that provide access between departments.

1.13 Spaces for general traffic allow for the circulation of ambulant and semi-ambulant people (including those using crutches, sticks and walking frames) and wheelchair users.

1.6 Although primarily applicable to new buildings, the recommendations contained within this Health Building Note should also be applied, where practical, when existing facilities are being upgraded.

1.14 The dimensions for wheelchair circulation relate to a standard 8L wheelchair (see Figure 1).

Supporting Health Building Notes

1.7 Where special departmental requirements warrant a variation from the spaces described in this document, information is provided in the relevant Health Building Note.

[HBN 00-04 – PDF page 13]

Figure 1 Dimensions of an occupied 8L wheelchair

• a bariatric bed, for patients weighing up to 450 kg (1000 lbs), that is 2330 mm × 1080 mm.

space for occupied chair

Note

Larger/wider bariatric bed usage is not covered in this Health Building Note.

1.17 Consideration should be given to other specialist beds that may be used.

rests

1050–1200

760–815

1.18 The dimensions included in the example drawings may include:

leg rests

standard

seat depth space for

330–385

space for occupied chair, standard leg

• a recommended dimension or range of dimensions;

space for occupied chair, extended leg rests

space for extended leg rests

• a recommended minimum dimension – shown in brackets, where included.

Figure 2 Dimension standards

Note

X or X–Y

(Z)

X = Recommended dimension X–Y = Recommended range of acceptable dimensions Z = Recommended minimum dimension

The overall dimension of an occupied 8L wheelchair (approximately 1500 mm × 800 mm) is similar to the space requirements of an electrically propelled wheelchair (see table E2 in BS 8300). However, some electric scooters are larger and some wheelchairs have different proportions (for example, sports wheelchairs may be 1000 mm wide).

1.19 The dimensions for circulation widths noted and illustrated in this Health Building Note should be unobstructed, and any projections should be avoided, for example by recessing radiators and fire extinguishers.

1.15 Space recommendations take account of the inexperience of some users in manoeuvring wheelchairs or using walking aids, but do not take account of the use of specialist large wheelchairs or mobility scooters.

1.16 Space recommendations for bed movement allow for the circulation of:

• an extended standard hospital bed, with or without orthopaedic/other attachments, that is 2370 mm × 1000–1050 mm; and

1.20 Where doors open onto walls that include handrails, the dimensions provided assume that a door handle fixed at 1000 mm from the floor will pass over a handrail fixed at 900 mm from the floor. Door handles may be replaced by automatic door opening devices.