Schemes should maintain and enhance local biodiversity following local planning policy and, where applicable, meet statutory biodiversity net gain (BNG) requirements, using high‑quality

landscape design to deliver both ecological and health benefits. Business cases should ensure sufficient provision is made within the cost plan to achieve and maintain landscape quality throughout the project lifetime. Nature‑based solutions should be prioritised wherever

possible to deliver health, biodiversity and climate resilience benefits.

Key components for external spaces are:

• gardening

• sport

• creativity

• art

• education

• exercise

• play

Travel and access

Neighbourhood health centres will be planned to promote sustainable travel choices and enable convenient access for all members of the community. Site selection and design should prioritise strong public transport links, safe and direct pedestrian routes, and high- quality cycling infrastructure, including secure cycle storage and facilities that support active travel. Centres should be easy to reach without a car wherever possible, reducing reliance on private vehicles and encouraging healthier, low-carbon modes of travel.

Parking provision will be informed by local planning policy and the available public transport

in the area, recognising the differences between inner-city locations with good public transport access and rural or suburban settings with limited connectivity. Parking should be sensitively integrated into the site and offer affordable electric vehicle charging facilities. Designs should avoid isolating the building behind extensive surface parking and incorporate landscaping to create a welcoming, accessible environment.

Travel and external access arrangements must be developed in partnership with a disability reference group, including people with sensory, physical and cognitive disabilities, to ensure that routes, drop-off points and building entrances are inclusive and intuitive. Opportunities to

share parking or travel infrastructure with neighbouring organisations should also be explored early in the design process.

[Neighbourhood health centres – PDF page 26]

Buildings

Neighbourhood health centres are based on a library of repeatable rooms and room clusters that can be assembled in different functional configurations to meet the clinical brief.

The adaptability of these centres throughout their 50+ year planned life and beyond is essential and every project will consider how the building will need to change over time.

Neighbourhood health centres will accommodate known NHS models of care from the outset but have the flexibly to adapt to new models throughout their operational life. Designers should consider whether the space could be converted, in part or whole, to other potential

uses such as housing or commercial.

Each neighbourhood health centre will have a shared entrance space that acts as the focal point for welcome and orientation and the front door for access to all services operating in the building. This public zone will have digital check-in, a single shared reception desk and clear signposting, creating a simple and consistent experience for all visitors. From this shared space, people will move into the clinical areas and the wider community facilities, including spaces such as group rooms and community support rooms.

The proposed form of tenure, will enable a ‘neutral’ public zone, providing the

accommodation for all public functions such as welcome, information, waiting and public toilets. Tenure and ‘plug in, plug out’ adaptability will mean that the public zone will be separate from the clinical, social and third party clusters.

Layouts and wayfinding strategies recognise that neighbourhood health centres are public buildings with public responsibilities yet contain mainly private functions. Patients and staff will be able to move around the building, and find their way easily and enjoyably, understanding how the centre works and gaining a sense of control.

Healthcare buildings will have qualities that reflect and promote a healthy lifestyle for patients, staff and visitors:

• well-tempered environments that provide patients, visitors and staff with those elements that are essential to our health, such as fresh and gently moving air, well balanced temperatures, good acoustics, high levels of day light penetration, sunlight without glare and the use of contrasting and changeable levels of lighting

• materials and finishes that have a zero or very low volatile organic compounds content and low embedded carbon

[Neighbourhood health centres – PDF page 27]

• healthy environments, wherever possible, that assist us in our daily lives to maintain a

healthy lifestyle, for example, good food, social interaction, access to sunshine, nature, exercise and the arts

The building is constructed using good materials and finishes that maintain their quality. A level of detail in the design communicates that care and thought have gone into making the building fit for the patients and the staff.

Neighbourhood health centres provide a collaborative environment in which staff can work and learn together in multidisciplinary teams in safety, while also supporting their morale. The relationship between workplace design and wellbeing is an essential component in

improving productivity, recruitment and retention.

Planning principles

New-build neighbourhood health centres will be planned on a standardised structural grid. This enables the clustering of rooms in an interchangeable configuration to maximise

adaptability – the ‘long life, loose fit’ approach to their design, and offers opportunities for MMC, off-site manufacture and the development of standard product and mechanical, electrical and plumbing (MEP) assemblies.

We have chosen a grid of 8.1m x 7.2m as this size can accommodate a wide range of clinical and social functions. Local solutions may adapt the form of the building to suit site constraints, adhering to the building principles set out in this specification.

A standard set of room sizes from the revised HBN 00-03; Clinical and clinical support spaces (2026) can accommodate all required functions in various configurations, again to ensure long life adaptability and to maximise the advantages of assembling these buildings from a standard set of high-quality components. For the programme to benefit from

scalability and repeatability, designs will use these standard room sizes wherever possible.

Within HBN 00-03; Clinical and clinical support spaces there are 2 sizes for consulting and examination rooms: 13.5 or 16 square metres. The latter can provide 3-sided couch access or, by aligning the couch against one wall, leave additional space in the room for escorts or family accompanying a patient or to place mobile equipment. When planning a centre, the appropriate ratio of 13.5 to 16 square metres sized rooms to meet the brief requirements should be considered, as well as how this fits efficiently within the chosen grid spacing.

To meet net zero carbon requirements and deliver the required percentage of MMC, an all- electric approach to the provision of building services is adopted. This increases the size of plant areas and primary distribution risers and horizontal runs. To provide sufficient depth for

[Neighbourhood health centres – PDF page 28]

above ceiling services a repeatable floor to floor height of 4,000mm will accommodate floor

to ceiling heights of circa:

• 2.55m in double loaded corridors • 2.7m in consultation and examination and treatment rooms • 3m in group and therapy rooms and single loaded primary circulation routes

Columns are standardised as a zone of around 450 millimetres square to allow for differences in structural methodologies, and layouts should be planned so that columns do not land within offices, consultation rooms or circulation areas, MEP zones and manufactured partitions. 150mm partition walls are used in the examples developed to meet

acoustic, fire safety, robustness and MCC requirements. The walls around the stair and lift cores are at least 250mm to support consistent riser positioning, modular core walls and prefabricated structural/stability elements.

Riser positions should be consolidated into 2 to 4 major stacks, sized for prefabricated MEP riser frames. These should be in the centre of the race-track solutions (typically where support clinical rooms are located) to allow service distribution to the wings or quadrants without having cross-overs and maximise standardisation. 1,800mm corridor widths are included throughout to support MEP services distribution routes.

Adopting standardised assemblies for the shell and core design include but are not limited to:

• circulation cores; lifts and stair modules • façade modules and assembles • horizontal and vertical service zones • defined allowance for future plant capacity

The incorporation of these strategies is reflected in the planning, circulation and engineering

allowance percentage uplift in the schedule of accommodation.

Room assemblies

The standard rooms will be assembled to provide maximum flexibility of use in the clinical zone between general practice, community care and secondary care clinic rooms. Placing clinical rooms on an outside wall and the supporting rooms in a central core reduces the length of the clinical building zones.

These planning principles and room assemblies deliver a building that is inherently flexible, as the public circulation or waiting areas are ‘neutral’ under the landlord’s control, separated

from the ‘plug in, plug out’ health, social care and community components that can agilely respond to change.

[Neighbourhood health centres – PDF page 29]

Figure 1 illustrates the indicative number of patient-facing rooms by room type for a typical

core, core+ and core++ model. The numbers within it are drawn from the published schedule of accommodation and show how spatial provision increases as the service offer expands. Rooms have been deliberately selected for multi-use, with flexibility built in to maximise utilisation while remaining closely aligned to the types of services expected to operate within each space. This approach avoids unnecessary oversizing and ensures that rooms are proportionate, functional and fit for purpose. The diagram is intended to demonstrate the underlying rationale that services can be delivered via these typical rooms within the schedule of accommodation, timetabled on a sessional basis to increase utilisation of the rooms, rather than being owned full time by a particular service.

Figure 1 - indicative number of patient-facing rooms by room type for a typical core, core+ and core++ model

Product assemblies

In new-build schemes, a standardised kit of parts underpins consistent internal layouts and operational efficiency across the programme, while providing sufficient flexibility for the

building form and external envelope to be locally designed in response to environmental conditions, urban context and community identity.

The ProCure Framework (on the Futures collaboration platform; login required) product range will be the starting point but will require continuous review and continuous refreshing to minimise embedded carbon and eliminate volatile organic compounds in products as a pass or fail approach to materials.

Facilities management

Strong facilities management practices will be built into the programme to support the digital and smart building strategy. These practices will be enabled through the NHS digital toolkit

[Neighbourhood health centres – PDF page 30]

and the buildings digital asset management solution, which will provide a consistent way to manage building and asset information from design through to day‑to‑day operation.

This approach will avoid teams working in silos. Instead, it will encourage joined‑up, evidence‑based decisions that focus on practical outcomes and long‑term performance.

The main design team should be supported by asset management (digital) specialists, operational estates and facilities management (EFM) teams and building information management (BIM) experts. This wider team will ensure buildings are designed to be operated, not just designed and handed over, reducing risk and improving long-term value.

Neighbourhood health centres will have a single point of day-to-day control, providing both real-time visibility and strategic insights into overall performance across the building, estates, facilities and engineering teams’ activities and business processes.

Neighbourhood health centre teams, including the building contractor, will provide a detailed commissioning strategy prior to practical completion of the building works. The plan will adequately evidence commissioning, sign-off processes and training; handover of quality documentation; ensure minimal defects and later disruption to the service via an early agreed soft landings approach; and identifying specifics that need to be introduced to the FM

teams, centre manager and end users.

As part of scheme development and operation, neighbourhood health centre teams should consider proportionate security and counter-terrorism measures appropriate to the scale, use and risk profile of the site. While many centres may fall below the statutory thresholds of the Terrorism (Protection of Premises) Act, schemes should be informed by relevant national

guidance and undertake appropriate risk assessment, including consideration of safe access and egress, public zone management, physical mitigation measures where appropriate, and operational procedures to support preparedness and response.

This approach will maximise the reliability and availability of critical building assets by integrating with other key control systems, exploiting data to automate workflow, optimise internal and external ‘resources’ and drive compliance and reporting.

Fire safety

Neighbourhood health centres will be designed to ensure the safety of all users. Compliance with the functional requirements of the Building Regulations 2010 (as amended) may be demonstrated using HTM 05 02: Fire safety in the design of healthcare premises, read

alongside Approved document B (Fire Safety), volume 2. Buildings other than dwellings. It is acknowledged that based on the patient dependency not all aspects of the HTM guidance

[Neighbourhood health centres – PDF page 31]

may be applicable to all neighbourhood health centres and so reference to both will be

required.

Each neighbourhood health centre must have a site-specific fire strategy, prepared by a competent person such as an independent expert adviser (AE), authorised person (fire projects – see HTM 05-01: Managing healthcare fire safety) or fire engineer if fire engineering is involved (see HTM 05-03, part J: Guidance on fire engineering of healthcare premises). The fire strategy will be robust and flexible enough to ensure safety at all times.

As a minimum, this strategy must reflect or address:

• the level of patient dependency. This will significantly influence the fire strategy: for example, where patients may be given local anaesthetics, that may impinge or their mobility and means of escape • any local fire hazards such as the use of medical gases or the risk of arson • space adjacencies, compartmentation, detection and alarm requirements, means of escape • business continuity in case of fire • ongoing maintenance of fire elements and the fire performance of the building fabric

The strategy will be robust and flexible enough to ensure safety at all times. Each neighbourhood health centre will provide an individual, site specific, fire strategy report which considers the patient dependency, local fire hazards, adjacencies, compartmentation, alarm requirements and fabric performance requirements.

The Building Safety Act 2022, and particularly the classification of a “Higher Risk Building”

may apply to these buildings if forming the base of a residential development. Refer to NHS Estates Technical Bulletin (NETB) No. 2024/2, Building Safety Act (2022) – application to healthcare buildings for guidance.

Standalone 2storey healthcare buildings are typically not higher risk buildings, but the building safety act (BSA) duty holder competence and strengthened building control requirements still apply.

Area zoning: public spaces

The civic nature of neighbourhood health centres means that their ‘public’ areas will provide much more than basic clinical waiting and circulation space. There will be active, flexible spaces that promote ‘wellness’ and community activity rather than purely functional content.

Public zones will provide:

• welcome meet and greet space • check in and reception

[Neighbourhood health centres – PDF page 32]

• vertical and horizontal circulation • waiting areas • patient toilets • changing places or toilets • interview rooms • multifunctional group rooms • gardens

The public zone can also be used to support wider place making ambitions, and organisations should consider how this space could accommodate locally appropriate community uses. For example, entrance areas could be designed to host social enterprise

cafés, community kitchens, informal gathering spaces or small education or digital access points. While these elements are not included in the core schedule of accommodation, local partners may choose to incorporate such features so public spaces maximise shared value for the benefit of the neighbourhood and support community outcomes.

A principal feature in neighbourhood health centres is connecting these spaces in both tenure and socially, recognising that these centres will be a focus within their communities for a wide range of activities. These design principles support the ambitions to address the social determinants of health through fostering strong community cohesion and empowerment.

The entrance itself will be easily identified, accessible and present positive first impressions for patients and staff, with a priority given to the provision of green spaces viewed from circulation and waiting areas.

Discrete areas can be secured when not in use while allowing other areas to be used as normal without enhanced security measures.

Consideration will be given to colour palettes and the user experience of these areas. They

will be welcoming, calming and attractive places, shaped by the community, and not overly clinical in appearance.

Rooms that are multifunctional, including for use as a meeting space, group therapy room or education space, can be located in the public zone and may be designed for community use outside normal working hours. There is scope in the accompanying layouts to open up the group rooms to create a larger hall that the community can use.

The public will be able to easily access all spaces within the public zone. Access control to all spaces in the public zone will be minimal to allow their easy access by the public, but the

capability to keep these spaces under active and passive surveillance is important.